Product Specifications
Manufacturer:Amphenol Advanced Sensors (Telaire)
Model Series:T8000-R (T8100-R, T8200-R)
Type:Wall Mount CO₂ and Temperature Transmitter
Sensing Method:NDIR (Non-Dispersive Infrared), gold-plated optics
CO₂ Measurement Range:T8100-R: 0-2000 ppm; T8200-R: 0-5000 ppm
CO₂ Accuracy:±30 ppm or ±3% of reading (whichever is greater)
Temperature Range:0 to 50°C (32 to 122°F)
Temperature Accuracy:±1°C (15-30°C range)
Output Options:0-5V, 0-10V (switch selectable), or 4-20 mA (maximum load 500 Ω); plus relay
Relay Rating:1A @ 24 VDC, 0.5A @ 125 VAC
Power Supply:18-30 VAC RMS, 50/60 Hz, or 18-42 VDC (polarity protected)
Power Consumption:0.7 W typical at 24 VAC
Warm-up Time:<2 minutes operational; 10 minutes to full accuracy
Stability:<2% of FS over sensor lifetime (15 years typical)
Operating Conditions:0 to 50°C, 0 to 95% RH non-condensing
Enclosure Rating:Flame retardant UL94 5VA
Mounting:Wall mount with tamper-resistant locking screw
Software:UIP software compatible for customization
Compliance:CE, RoHS, REACH, WEEE
Product Description
The Telaire T8000-R Series is a low-cost, high-performance wall mount CO₂ and temperature transmitter designed for building automation and indoor agriculture markets. It integrates seamlessly with building management systems to enable demand-controlled ventilation, reducing energy costs while maintaining indoor air quality compliance .
The transmitter features a patented NDIR (Non-Dispersive Infrared) gas sensing engine with gold-plated optics, delivering high accuracy in a compact package. The patented ABC Logic™ self-calibration system automatically corrects for long-term drift in most applications, eliminating the need for manual calibration and providing a lifetime CO₂ calibration warranty .
Two models are available: the T8100-R with 0-2000 ppm range (ideal for ASHRAE-compliant indoor air quality monitoring), and the T8200-R with 0-5000 ppm range for applications requiring extended measurement capability. Accuracy is ±30 ppm or ±3% of reading, whichever is greater . Temperature measurement is included with accuracy of ±1°C from 15-30°C .
The built-in relay provides flexible control options—it can actuate ventilation fans when CO₂ exceeds setpoints in buildings without automation systems, or control CO₂ enrichment equipment to optimize plant growth in indoor agriculture applications. Output options include field-selectable 0-5V, 0-10V, or 4-20mA analog signals .
Installation is simplified with a mounting plate featuring two-piece terminal blocks for quick wiring. A gas-permeable, water-resistant diffusion filter protects the sensor from particulate and moisture contamination. The locking screw secures the cover to the mounting bracket for tamper resistance .
All units are factory calibrated and feature conformal coating on 5000 ppm models for enhanced protection. The modern enclosure design suits a variety of indoor environments. UIP software is available for custom configuration .
Applications
- Building automation and demand-controlled ventilation
- Indoor agriculture and greenhouse CO₂ enrichment
- Classroom, conference room, and meeting hall air quality monitoring
- HVAC system integration and energy management
Features
- Patented NDIR sensing engine with gold-plated optics
- ABC Logic™ self-calibration – no manual calibration required in most applications
- Lifetime CO₂ calibration warranty
- Selectable output options: 0-5V, 0-10V, or 4-20 mA
- Built-in relay for ventilation or CO₂ enrichment control
- Gas-permeable, water-resistant diffusion filter
- Tamper-resistant locking screw
- Two-piece terminal blocks for easy wiring
- Factory calibrated; conformal coating on 5000 ppm models
- CE, RoHS, REACH, WEEE compliant
Wall Mount CO₂ Transmitter - NDIR, Relay Output | Telaire T8000-R Series
Product Specifications
Manufacturer:Amphenol Advanced Sensors (Telaire)
Model Series:T8000-R (T8100-R, T8200-R)
Type:Wall Mount CO₂ and Temperature Transmitter
Sensing Method:NDIR (Non-Dispersive Infrared), gold-plated optics
CO₂ Measurement Range:T8100-R: 0-2000 ppm; T8200-R: 0-5000 ppm
CO₂ Accuracy:±30 ppm or ±3% of reading (whichever is greater)
Temperature Range:0 to 50°C (32 to 122°F)
Temperature Accuracy:±1°C (15-30°C range)
Output Options:0-5V, 0-10V (switch selectable), or 4-20 mA (maximum load 500 Ω); plus relay
Relay Rating:1A @ 24 VDC, 0.5A @ 125 VAC
Power Supply:18-30 VAC RMS, 50/60 Hz, or 18-42 VDC (polarity protected)
Power Consumption:0.7 W typical at 24 VAC
Warm-up Time:<2 minutes operational; 10 minutes to full accuracy
Stability:<2% of FS over sensor lifetime (15 years typical)
Operating Conditions:0 to 50°C, 0 to 95% RH non-condensing
Enclosure Rating:Flame retardant UL94 5VA
Mounting:Wall mount with tamper-resistant locking screw
Software:UIP software compatible for customization
Compliance:CE, RoHS, REACH, WEEE